Instrumentation Cables | ||||||||||||||
EN 50288-7 Instrumentation Cables
XLPE Insulated, LS ZH Sheathed & Overall Screened Instrumentation Cables (Single
Pair)
RE-2X(St)H 90°C / 300V
STANDARDS
Basic design to EN 50288-7
Applications
The unarmoured LSZH sheathed cables are generally use for indoor installation and suitable for wet
and damp areas. Generally, the cables are used within industrial process manufacturing plants for
communication, data and voice transmission signals and services. Also used for the interconnection
of electrical equipment and instruments, the LSZH sheath can reduce toxic smoke and fume
emission.
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)*** |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance** | ICEA S-73-532 |
60% of tensile strength/min.60% of elongation, *** denotes optional.
VOLTAGE RATING
300V
CABLE CONSTRUCTION
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Binder tape: PETP transparent tape
Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in
contact with tinned copper drain wire, 0.5mm²
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting
LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon
resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems
Physical AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +90°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 7.5 X Overall Diameter
CONSTRUCTION PARAMETERS
Caledonian Cable Code | RE-2X(St)H | ||||
No. of Pairs x2xCross Section |
Nominal Insulation Thickness |
Nominal Outer Sheath Thickness |
Nominal Overall Diameter |
Approx. Weight |
|
No.x2xmm2 | mm | mm | mm | kg/km | |
RE-2X(St)H 1P0.5 | 1x2x0.50 | 0.35 | 0.8 | 5.2 | 38 |
RE-2X(St)H 1P0.75 | 1x2x0.75 | 0.38 | 0.8 | 5.6 | 49 |
RE-2X(St)H 1P1.0 | 1x2x1.0 | 0.40 | 0.9 | 6.3 | 56 |
RE-2X(St)H 1P1.3 | 1x2x1.3 | 0.45 | 0.9 | 6.8 | 65 |
RE-2X(St)H 1P1.5 | 1x2x1.5 | 0.45 | 0.9 | 7.1 | 71 |
Electrical PROPERTIES
Conductor Area Size | mm 2 | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 | |
Insulation thickness (nominal) | mm | 0.4 | 0.4 | 0.4 | 0.45 | 0.45 | |
Conductor resistance (20°C) | Ω/km | 36.7 | 25 | 18.5 | 14.2 | 12.3 | |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | |||||
Mutual Capacitance (1 kHz) | pF/m(Max.) | 115 | |||||
≤ 4 pairs | 90 | 90 | 90 | 102 | 102 | ||
all other pairs | 75 | 75 | 75 | 85 | 85 | ||
Capacitance unbalance(1 kHz) | pF/500 m (Max.) | 500 | |||||
Inductance | mH/km (Max.) | 1 | |||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 | |
Operating voltage Urms | V | 300 | |||||
Test Voltage |
Core to Core | V | 1500 | ||||
Core to Screen | V | 1500 |