Instrumentation Cables 

   EN 50288-7 Instrumentation Cables
XLPE Insulated, LS ZH Sheathed & Overall Screened Instrumentation Cables (Single Pair)
RE-2X(St)H 90°C / 300V

EN 50288-7 Instrumentation Cables

STANDARDS
Basic design to EN 50288-7

Applications
The unarmoured LSZH sheathed cables are generally use for indoor installation and suitable for wet and damp areas. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the LSZH sheath can reduce toxic smoke and fume emission.

FIRE PERFORMANCE

Flame Retardance (Single Vertical
Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE
0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation
(Vertically-mounted bundled wires
& cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance** ICEA S-73-532
Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min
60% of tensile strength/min.60% of elongation, *** denotes optional
.

VOLTAGE RATING
300V

CABLE CONSTRUCTION
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Binder tape: PETP transparent tape
Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

COLOUR CODE
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +90°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 7.5 X Overall Diameter

CONSTRUCTION PARAMETERS

Caledonian Cable Code RE-2X(St)H
No. of Pairs
x2xCross Section
Nominal
Insulation
Thickness
Nominal
Outer Sheath
Thickness
Nominal
Overall
Diameter
Approx. 
Weight
No.x2xmm2 mm mm mm kg/km
RE-2X(St)H 1P0.5 1x2x0.50 0.35 0.8 5.2 38
RE-2X(St)H 1P0.75 1x2x0.75 0.38 0.8 5.6 49
RE-2X(St)H 1P1.0 1x2x1.0 0.40 0.9 6.3 56
RE-2X(St)H 1P1.3 1x2x1.3 0.45 0.9 6.8 65
RE-2X(St)H 1P1.5 1x2x1.5 0.45 0.9 7.1 71
Note : Other conductor sizes & core configurations are available upon request.

Electrical PROPERTIES

Conductor Area Size   mm 2   0.5  0.75   1.0   1.3 1.5  
Insulation thickness (nominal) mm 0.4 0.4 0.4 0.45 0.45
Conductor resistance (20°C)   Ω/km  36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz)  pF/m(Max.)  115
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz)  pF/500 m (Max.) 500 
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300

Test Voltage 

Core to Core  1500 
Core to Screen  1500